Effects of target additions to water on the efficiency of fire extinguisher
DOI:
https://doi.org/10.33408/2519-237X.2017.1-1.35Keywords:
fire extinguishing solution, target additives of complex action, extinguishing system, fire-extinguishing efficiency, pressure lossAbstract
Purpose. To conduct full-scale researches to determine the effect of water fire extinguishing solution on the hydraulic head loss in fire extinguishing pipeline and determin the relative effectiveness of the fire-extinguishing sprinkler system at natural firing tests.
Methods. In the work is used the methodology of field tests for studying the relative efficiency of water fire extinguishing agent during fire extinguishing. The research results have been treated by methods of computational mathematics using the software «Microsoft Office».
Findings. The results of experimental studies to determine the effect of specific additives to the water of complex action on the basis of sodium liquid glass Na2SiO3 and potassium carbonate K2CO3 on hydraulic characteristics and the effectiveness of fire extinguishing sprinkler systems are presented. The relative effectiveness of fire extinguishing sprinkler systems filled with investigated extinguishing water solution as compared to the sprinkler system filled with water without any special additives for extinguishing the model Class 13A fire is determined under the similar conditions of full-scale fire tests.
Application field of research. The proposed water fire extinguishing solution is designed for the use in the sprinkler system which is separated from the system of domestic and drinking water supply system.
Conclusions. The efficiency of specific additives to water of complex action on the basis of sodium liquid glass Na2SiO3 and potassium carbonate K2CO3 is proved to reduce hydraulic losses in the fire extinguishing system and improve the efficiency of fire extinguishing.
References
National Building Codes V.2.5-64-2012 Internal water supply and sewerage. Part I. Design. PART II. Building. Order of the Ministry of Regional Development of Ukraine by 31.10.2012 No. 553. 168 p. (ukr)
National Building Codes V.2.2-24: 2009 Buildings and constructions. Designing high-rise residential and public buildings, Ministry of Regional Development of Ukraine the order by 12.02.2009. No. 67. 114 p. (rus)
Building Standards Belarus 4.01.02-03 Fire water supply. Ministry of Architecture and Construction of Belarus, the Technical Committee № 03 «Fire Safety» (Republic of Belarus). Order of the Ministry of Architecture and Construction of Belarus from 30.12.2003. No. 259. 24 p. (rus)
Technical Code of Good Practice 45-3.02. High-rise building construction design standards. Order of the Ministry of Architecture and Construction of Belarus of June 12, 2008. No. 197. 98 p. (rus)
Regional Building Code 31-332-2006 Residential and public high-rise buildings. Adopted and put into effect the order of the Construction Committee of St. Petersburg Government of 23.12.2005 No. 68. 60 p. (rus)
Zhartovsky S., Sizikov A., Nizhnyk V., Ballo Y., Kopilniy N. Determination of chemical parameters of water fire extinguishing agents at their long sojourn in steel pipe fire suppression system. Proc. XVIII All-Ukrainian scientific-practical conference «Modern state of civil protection in Ukraine: prospects and ways of European space». Kyiv, 2016. 139 p.
Sizikov A., Uhansky R., Ballo V., Ballo Y. Design features zoned systems of internal fire water supply in buildings with a conditional height above 26.5 m. Journal of UkrNIIPB. Kyiv: UkrNIICP, 2014. No. 1 (29). 30-36 p. (ukr)
Zhartovsky S., Sizikov A., Nizhnyk V., Ballo Y., Ballo V. Features of influence of special additives in the composition of water fire extinguishing substances to the loss of pressure in the pipeline. Scientific-practical collection of problems of water supply and sewerage. Kyiv: KNUBA 2016. No. 26. 21-26 p. (ukr)
Zhartovsky S., Nizhnyk V., Uhansky R., Ballo Y. Identification of the influence of the chemical composition of water fire extinguishing agents based on Na2SiO3 K2CO3 and their effectiveness in extinguishing Class A Proc. International scientific-practical conference «Theory and practice of fire extinguishing and liquidation of emergency situations». Cherkasy. 2016. 46-49 p. (ukr)
Antonov A. [et al.]. Research on the features of the disclosure process termination burning of combustible materials in the application of modern fire extinguishing substances and technologies of their presentation. K. : UkrNIICP, 2015. 147 p. (ukr)
Methods № 93-2007 «Tests to determine the sprinkler discharge coefficient». K : UkrNIIFP, 2007. 17 p. (ukr)
State Standard EN 12259-1: 2008 (EN 12259-1: 1999, IDT) Fixed firefighting systems. Elements of sprinkler and drenchers. Part 1: Sprinklers K. : (UkrNIIPB). 118 p. (ukr)
Zalutsky E.V. Analysis of the daily operation of pumping stations: guidelines for the implementation of individual tasks with the workshop «Pump and blower station» For bachelors of construction for students specialty «Water and Sanitation» KNUBA. K., 2012. 28 p. (ukr)
Sawn timber and wood elements. Methods for determination of moisture GOST 16588-91, introduced 1993.01.01. 5 p. (rus)
DSTU EN 3-7: 2014 Fire extinguishers. Part 7: Characteristics, performance requirements and test methods Parameter (EN 3-7: 2004 + A1: 2007, IDT) order of Ministry of Economic Development of Ukraine of 30.12.2014, No. 1494. 157 p. (ukr)
Published
How to Cite
License
Copyright (c) 2017 Sizikov A.A., Zhartovskiy S.V., Nizhnik V.V., Ballo Ya.V., Benedyuk V.S.CC «Attribution-NonCommercial» («Атрибуция — Некоммерческое использование») 4.0