Current state of the problem of evaluating the influence of the horizontal openings in the separating structures on the fire temperature in the compartment

Authors

  • Aleksandr G. Ivanitskiy Ministry for Emergency Situations of the Republic of Belarus; ul. Revolyutsionnaya, 5, Minsk, 220030, Belarus
  • Alena V. Kolb State Educational Establishment «University of Сivil Protection of the Ministry for Emergency Situations of the Republic of Belarus»; ul. Mashinostroiteley, 25, Minsk, 220118, Belarus

DOI:

https://doi.org/10.33408/2519-237X.2017.1-4.402

Keywords:

calculation, fire temperature, integral model, horizontal opening, algorithm

Abstract

Purpose. The paper is devoted to analysis of experimental study and evaluation of the influence of the horizontal opening on the temperature of the fire in the compartment. The limitations of the previous scientific results in modeling fires are shown.

Methods. Compartment having both vertical and horizontal openings. To analyze the difference in fire temperature in the compartment Fire Dynamic Simulator has been used.

Findings. An analysis of literature sources and modeling of wood burning in an administrative compartment for evaluating the influence of the horizontal opening on the temperature of the fire in the compartment. A significant effect of ventilation through horizontal openings on the fire temperature is detected. Modification of the algorithm used in the development of the calculation methodology is suggested.

Application field of research. The results can be applied in calculating the compartment fire temperature taking into account the horizontal openings.

Conclusions. Horizontal openings have a significant influence on the fire temperature and should not be ignored during the calculation. It is necessary to revise the calculation algorithm used in the STB 11.05.03 methodology.

Author Biographies

Aleksandr G. Ivanitskiy, Ministry for Emergency Situations of the Republic of Belarus; ul. Revolyutsionnaya, 5, Minsk, 220030, Belarus

Head of Department; PhD in Technical Sciences, Associate Professor

Alena V. Kolb, State Educational Establishment «University of Сivil Protection of the Ministry for Emergency Situations of the Republic of Belarus»; ul. Mashinostroiteley, 25, Minsk, 220118, Belarus

Chair of Fire Safety, Lecturer

References

Technical Regulation ТR 2009/013/BY* Zdaniya i sooruzheniya, stroitel'nye materialy i izdeliya. Bezopasnost' [Buildings and structures, constructional materials and units. Safety]. The full-text information retrieval system «StroyDOKUMENT» [Electronic resource]. Electronic text data and programs (700 Mb). Minsk, RUE «Stroytechnorm», 2007. 1 electronic optical disc (CD-ROM). (rus)

Svetoprozrachnye konstruktsii. Organizatsiya mebel'nogo i lesopil'nogo proizvodstva [Translucent constructions. Organizing of sawmill and cabinet making]. LLC «М8 City». 2017, availiable at: http://m8city.by/projects/188/. (accessed: July 01, 2017) (rus)

Standard STB 11.05.03-2010 Sistema standartov pozharnoy bezopasnosti. Pozharnaya bezopasnost' tekhnologicheskikh protsessov. Metody otsenki i analiza pozharnoy opasnosti. Obshchie trebovaniya [System of fire safety standards. Fire safety in industrial processes. Methods of evaluation and analysis of fire hazard. General requirements]. Affirmed 28.04.2010. State Council for standardization of the Republic of Belarus, availiable at: http://tnpa.by/ViewFileText.php?UrlRid=106043&UrlOnd=%D1%D2%C1%2011.05.03-2010 (accessed: July 01, 2017). (rus)

Standard GOST R 12.3.047 Sistema standartov bezopasnosti truda. Pozharnaya bezopasnost' tekhnologicheskikh protsessov. Obshchie trebovaniya. Metody kontrolya [System of labor safety standards. Fire safety in industrial processes. Methods of evaluation and analysis of fire hazard. General requirements. Control methods]. Affirmed 01.01.2014. Мoscow: FSBA «VNIIPO» MES of Russia, 2014. 66 p. (rus)

Metody rascheta temperaturnogo rezhima pozhara v pomeshcheniyakh zdaniy razlichnogo naznacheniya. Rekomendatsii [Calculation methods of fire temperature in enclosures of functional buildings. Recommendations]. Мoscow: VNIIPO MIA USSR, 1988. 56 p. (rus)

Molchadskiy I. Rukovodstvo po raschetu temperaturnogo rezhima pozhara v pomeshcheniyakh zhilykh zdaniy [Guide for calculation of fire temperature in rooms of residential buildings]. Мoscow: VNIIPO MIA USSR, 1983. 49 p. (rus)

Evrokod 1. Vozdeystviya na konstruktsii. Chast' 1-2. Obshchie vozdeystviya. Vozdeystviya dlya opredeleniya ognestoykosti [TKP EN 1991-1-2-2009. Eurocode 1: Actions on structures. Part 1-2: General actions – Actions on structures exposed to fire]. The full-text information retrieval system «Stroy-DOKUMENT» [Electronic resource]. Electronic text data and programs (700 Mb). Minsk, RUE «Stroytechnorm», 2007. 1 electronic optical disc (CD-ROM). (rus)

Shebeko Yu., Shebeko A., Gordienko D. Raschetnaya otsenka ekvivalentnoy prodolzhitel'nosti pozhara dlya stroitel'nykh konstruktsiy na osnove modelirovaniya pozhara v pomeshchenii [Effective estimation of equivalent fire duration for building structure on the basis of fire modeling in enclosure]. Fire safety. 2015. No. 1. Pp. 31-39. (rus)

Kurachenko I., Zhamoydik S., Nemurova A. Analiz podkhodov k opredeleniyu privedennoy vysoty proemov pri raschete temperaturnogo rezhima pozhara [Analysis of approaches to determining the weighted average of openings heights in calculating of the fire temperature]. Chrezvychaynst situatsii: preduprezhdenie i likvidatsiya [Emergency situations: prevention and elimination]. 2015. No. 1 (37). Pp. 79-86. (rus)

Heselden A.J.M. et al. Supplementary reports of work for the С.I.B. international co-operative research program on fully-developed fires: Fire Research Note No. 923 Fire research station. – BRE Trust: Borehamwood, Hertfordshire, 1972. 254 p., availiable at: http://www.iafss.org/publications/frn/923/-1/view/frn_923.pdf (accessed: July 01, 2017). (rus)

Yii, E.H. Modelling the effects of fuel types and ventilation openings on post-flashover compartment fires: PhD in fire eng. thesis E.H. Yii. – New Zealand: Univ. of Canterbury Christchurch, 2002. 328 p.

Lia Q., Zhanga J., Lua S. Influence of roof opening on gas temperature rise in an enclosure ScienceDirect. The 9th Asia-Oceania Symp. on Fire Science and Technology, China, Hefei, 17–20 oct. 2012; ed.: Naian Liu. Hefei, 2013. Vol. 62. Pp. 194–201, availiable at: http://www.sciencedirect.com/science/article/pii/S187770581301237X (accessed: July 01, 2017).

Heselden A.J.M., Wraight H.G.H., Watts P.R. Fire problems of pedestrian precincts. Part 2. Large-scale experiments with a shaft vent: Fire Research Note №954. Department of the environment and fire offices' committee Joint fire research organization. BRE Trust, 1972. 54 p. availiable at: http://www.iafss.org/publications/frn/954/-1/view/frn_954.pdf (accessed: July 01, 2017).

Philip J., DiNenno et al. Handbook of fire protection engineering. 3rd ed. – Quincy, MA: NFPA, SFPE, 2002. 1604 p.

Epstein M., Kenton M.A. Combined natural convection and forced flow through small openings in a horizontal partition, with special reference to flows in multicompartment enclosures. Journal of Heat Transfer, 1989. Vol. 111. No.4. Pp. 980-987.

Tan Q., Jaluria Y. Flow through horizontal vents as related to compartment fire environments: Report National inst. of standards and technology. Gaithersburg, MD, 1992. 104 p. No. NIST-GCR-92-607.

Than C.F., Savilonis B.J. Modeling fire behavior in an enclosure with a ceiling vent. Fire safety journal, 1993. Vol. 20. No. 2. Pp. 151-174.

Bailey J.L., Williams F.W., Tatem P.A. Use of a zone model for validation of a horizontal ceiling/floor vent algorithm: Report Naval research lab. Washington, DC, 1991. 42 p. No. 6811.

Jansson R., Onnermark B., Halvarsson K. Fire in a roof-ventilated room: Report at. Defense Research Inst. Stockholm, 1986. 145 p. No. C 20606-D6.

Heiselberg P. Modelling of natural and hybrid ventilation: DCE Lecture Notes No 4. Aalborg Univ.: Department of civil eng. Aalborg, 2006, availiable at: http://vbn.aau.dk/en/publications/modelling-of-natural-and-hybrid-ventilation(e8c6f086-f42c-46b0-a67b-9fec1fc29541).html (accessed: July 01, 2017).

Cooper L.Y. Calculation of the flow through a horizontal ceiling floor vent. Gaithersburg, MD: National inst. of standards and technology, 1989. 25 p.

Li Z. Characteristics of buoyancy driven natural ventilation through horizontal openings: PhD in fire eng. thesis. Aalborg, 2007. – 118 р.

Ivannikov V., Klyus P. Spravochnik rukovoditelya tusheniya pozhara. Мoscow: Stroyizdat, 1987. 288 p. (rus)